Customization: | Available |
---|---|
Task: | Adjust |
Structure: | Combination |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Analog Input Isolation Conversion Redundant Board PHFD-16RAI
Number of channels: 16
Signal type: dual line analog input (temperature, voltage/current), three terminal isolation
Supporting isolation barrier: Pinghe Analog Input 1 in 2 out Rail Grid (12.8mm)
Installation form: M4.8 self tapping or M4 screw fixation
Supporting card components:
S7-300PLC: 6ES7 331-1KF02 \ 7KF02 \ 7NF00 \ 7NF10, etc.
This product does not support the 7KF02 loop power supply mode (range card D).
Common configurations:
Single channel 1 in 2 out analog input isolation gate: Pinghe single channel analog input 1 in 2 out rail grid (12.8mm)
Power supply and DB port power settings:
This product is designed for redundant
power supply and comes with a power loss alarm output
DB1 port contains a 4-core power cord for supplying power to the PLC module. These power supplies are controlled by short-circuit caps set by the power output, with each short-circuit cap corresponding to a wire, as shown in the upper right figure. Before power transmission, settings should be made as needed.
Parameter
Order model |
PHFD-16RAI |
describe |
Modular input isolation conversion redundant board |
Technical parameters |
|
Channel |
sixteen |
Number of isolation barriers |
16 single channel 1 in 2 out |
Internal power supply voltage |
22-30VDC redundant power supply |
Power loss alarm output |
normally closed |
Internal circuit current indication |
not have |
Maximum current of on-site side channel |
25mA |
Internal connection type |
D-SUB37PF *2 + HART |
On site side connection type |
screw |
Terminal crimping specifications |
0.3~2.5(mm2) |
signal type |
2-wire transmitter, four wire system signal, temperature signal |
Isolator output signal |
4-20mA 2-channel |
operation temperature |
-30ºC~+55ºC |
storage temperature |
-40ºC~+70ºC |
Dimensions (length x width x height) |
232X112*60mm |
Installation size |
M4.8 self tapping or M4 screw 223mm |
attachment |
|
Power insurance |
Fang Insurance 2A |
Matching Cable |
|
Order model (2 items) |
FL-37D-23A40-Y-Z-Xm |