Customization: | Available |
---|---|
Task: | Adjust |
Structure: | Combination |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Overview
Base plate mounted isolated safety barrier PHC-11HF-34 can convert the safety zone contact switch, logic level input into intrinsically safe equipment drive quantity, output to the hazardous area site, so as to control solenoid valves, acoustic and visual alarms and so on. Signal status indicator set red and yellow dual-color, alarm display red, output solenoid valve and other work display yellow.
The product needs independent power supply, power supply, input and output are isolated at three ends.
Main technical parameters
Number of channels: | one input and one output |
Safety side input: | |
Input signal: | contact control DC voltage |
Hazardous side output: | |
Output signal: | 22V~24V DC, UE/IE=10.3V/48mA |
Allowable inversion function: | K1 is set to ON side, circuit output inverted |
LED indicator: | yellow-output relay is in normal operating state |
Alarm relay function: | Set the dip switch K2 to "ON" side, the circuit selects the alarm function. Load resistance <50Ω, short-circuit alarm (SC); load resistance >10kΩ, open circuit alarm (LB) |
Alarm relay characteristics: | Response time: 20ms Driving capacity: 250V AC/2A, 30V DC/2A resistive loads Load type: resistive load |
Output accuracy: | 0.1%F.S (typical: 0.05%F.S) |
Response time: | 20ms to 90% of final value |
Temperature parameters: | operating temperature -20ºC~+60ºC; storage temperature -40ºC~+80ºC |
Air relative humidity: | 10%~95%RH without condensation |
Insulation strength: | intrinsically safe end and non-intrinsically safe end (≥3000V AC/min) |
Insulation resistance: | ≥100MΩ (input/output/power supply between) |
Electromagnetic compatibility: | in line with IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
Mean time to failure: | 100000 hours |
Wire requirements: | cross-section ≥ 0.5mm2; insulation strength ≥ 500V |
Applicable field devices: | audible and visual alarms, intrinsically safe solenoid valves |
Installation site: | installed in the safe zone, can be connected with the highest in Zone 0, IIC, Zone 20, IIIC hazardous locations of the intrinsically safe instrumentation |
Safety certification | |
Certification body: | National Explosion-proof Electrical Product Quality Supervision and Testing Center CQST |
Certification standard: | GB/T 3836.1-2021, GB/T 3836.4-2021 |
Explosion-proof symbol: | [Exia Ga]IIC, [Exia Da]IIIC |
Certified parameters (between terminals 1-2): | Um: 250V AC/DC, Uo=25.2V DC, Io=108mA, Po=0.68W, Co=0.107μF, Lo=2.8mH. |
Q:Do you accept OEM or ODM orders?
A: Yes.we do.Please let us know your requirements
Q: What is your MoQ?
A:No MOQ limits.1 piece for trial order at first is acceptable
Q:What is your warranty for your product?
A:2 years (2 years maintenance guaranteed for non-man-made damages)
Q: How do you assure the quality?
A: Attaching great importance to quality control,we check every step to make sure items in good quality.