Temperature Signals Converter Input Module Modbus RTU Protocol

Product Details
Customization: Available
Mathematical Model: Linear
Signal: Continuous
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2023

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
63
Year of Establishment
2004-01-13
  • Temperature Signals Converter Input Module Modbus RTU Protocol
  • Temperature Signals Converter Input Module Modbus RTU Protocol
  • Temperature Signals Converter Input Module Modbus RTU Protocol
  • Temperature Signals Converter Input Module Modbus RTU Protocol
  • Temperature Signals Converter Input Module Modbus RTU Protocol
  • Temperature Signals Converter Input Module Modbus RTU Protocol
Find Similar Products

Basic Info.

Model NO.
PHM-7730 Ex.
Material
PVC
Transport Package
Box
Trademark
Beijing Pinghe
Origin
Beijing
Production Capacity
3000/Month

Product Description


Temperature Signals Converter Input Module Modbus RTU Protocol

Product overview

This device excels in converting three-channel temperature signals within hazardous areas into digital signals, ensuring isolation for safety purposes. By adhering to the MODBUS RTU protocol, it seamlessly delivers these digital signals to compatible systems such as the PHM7100, PLC, or host computer systems. This ensures efficient and secure communication of critical temperature data, enabling effective monitoring and control in industrial environments.

 

TECHNICAL INDICATORS

Power supply

20~35VD

Input signal

RTD/TC/Resistor/mV signals

Input channels

3 channels

Communication interface

RS48

Communication protocol

MODBUS RTU

Cold end accuracy

1ºC

Temperature drift

0.005% F.S/ºC

Configuration mode

PC programmable

Dielectric strength

≥2500VAC (intrinsically safe terminal and non-intrinsically safe terminal)

Insulation resistance

≥100MΩ

Applicable field equipment

B, E,J, K, N, R, S, T  TC, or millivolt signal sensors two-wire or three-wire TC Cu50,Cu100,pt100,pt10

Temperature parameter

Continuous working temperature-20ºC-+60ºC, storage temperature:-40ºC~+85ºC

Relative air humidity

10%-95%RH without condensation

Explosion-proof sign

[Exia Ga] II C

Authentication parameters (between terminals 1-2-3, 4-5-6, 7-8-9)

Um=250V Uo=8.4V Io=31mA
Co=4.8μF Lo=20mH Po=65mW

Installation place requirements

Can be connected with intrinsically safe instruments in zone 0 with IIA, IIB, IIC dangerous gas

 


 

Product characteristic

 
1.Low power consumption, minimal temperature drift, and seamless automatic zero calibration make this device a reliable choice for various applications. Its support for hot-plug functionality adds to its convenience and versatility.
2.Embracing the MODBUS RTU communication protocol, this device ensures swift and efficient data transmission, boasting a communication rate of up to 115200bps. Users can count on its stability and efficiency in transferring data across systems.
3.Offering flexibility in power supply and communication, it accommodates two methods: backplane mounting rail and terminal, catering to diverse installation requirements.
4.When paired with the PHM-7100, it seamlessly integrates MODBUS TCP/IP support, streamlining installation and maintenance processes while enhancing data transmission performance.
5.Each input signal's RTD/TC/Resistor/mV settings can be easily configured through programming, empowering users to tailor the device to specific application needs with precision and ease.


Temperature Signals Converter Input Module Modbus RTU Protocol
Temperature Signals Converter Input Module Modbus RTU Protocol

Temperature Signals Converter Input Module Modbus RTU ProtocolTemperature Signals Converter Input Module Modbus RTU ProtocolTemperature Signals Converter Input Module Modbus RTU ProtocolTemperature Signals Converter Input Module Modbus RTU Protocol


Temperature Signals Converter Input Module Modbus RTU Protocol

 

Q:Do you accept OEM or ODM orders?

A: Yes.we do.Please let us know your requirements

Q: What is your MoQ?

A:No MOQ limits.1 piece for trial order at first is acceptable

Q:What is your warranty for your product?

A:2 years (2 years maintenance guaranteed for non-man-made damages)

Q: How do you assure the quality?

A: Attaching great importance to quality control,we check every step to make sure items in good quality.

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier