Customization: | Available |
---|---|
Task: | Adjust |
Structure: | Combination |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AO Isolation Backplane PHHS-16AO-M
Number of channels: 16
Mode: two-wire AO, three isolation
Signal type: current output
With MTL standard HART interface (required to declare before ordering)
Online test port(using XT801 tester)
Installation form: M5 screw fixing or 35mm rail installation
Matching card: C300 & 8-Serial 16AO card
Supporting barrier: PH series Single AO barrier, see the barrier instructions for details
Supporting isolator: PH series Single AO isolator, see the isolator manual for details
Common configurations:
Single output barrier: PHC-11HD-11
Power supply:
This product is designed for redundant power supply, with power loss alarm output.
Order model | PHHS-16AO-M |
Description | 16-ch AO backplane |
Technical parameters | |
Number of channels | 16 |
Supply voltage | 22 ~ 30VDC redundant power supply |
Power loss alarm output | Normal close |
Sys connection | D-SUB37P |
Power connection type | Screw |
Terminal crimp specification | 0.3~2(mm2) |
Signal type | Current signal |
Complete with barrier | PHC-11HD-11 |
Barrier Input Signal | 4-20mA |
Operating temperature | -40ºC~+55ºC |
Storage temperature | -40ºC~+70ºC |
Dimensions (L*W*H) | 292X174x70mm |
Install the screws | M5 4PCS |
Hole spacing | 279.4*101.6mm |
Enclose | |
PS fuse | 2Aφ5 glass tube |
Matching cable | |
Standard model | FL-37DS-23A32-HON32-DI/ADO-Xm |
Simple model | FL-37DS-23A32-H32-DI/ADO-Xm |
Loose line model | FL-37DS-23A32-H-DI/ADO-Xm |
Note: Horney terminal board shall be provided by the customer for X-length simple model |